Battery.runtime maximum at 65535 [Dell; rebranded Eaton?] #731
Comments
ups.test.result: Aborted
NUT gets the size of the variables from the USB HID descriptor. The 65535 is probably intended to be a 16-bit signed value of -1 for "unknown". I would recommend running a battery test, and seeing if the "ups.test.result" variable changes.
|
It does change as i have seen it loading the batteries and reaching the limit.
|
Closing since test seems to have fixed the reported value. |
After i saw you closed the bugfix I tried to investigate a bit more. Result: If the UPS load is below or equal to 10%, it does not calculate the runtime properly. There is also a paragraph in the manual saying, that a battery test can only be done with a load above 10%. However, last time it still started properly. So we can assume it's a Firmware issue. Some data
|
Some addon... Once the UPS is online again, it seems to do some calculations, but I doubt one can trust the values.
|
…rkupstools/nut#731] Signed-off-by: Jim Klimov <[email protected]>
…rkupstools#731, networkupstools#1740 et al] Signed-off-by: Jim Klimov <[email protected]>
Hi!
I'm using a Dell UPS 2700W with an extended Battery Modul (EBM).
As i have a quite low load on the UPS (about 5%) it's easy to reach a very high runtime (in sec)
For now it seems like i reached the max of a 16Bit variable.
Is this limit given by NUT? if so, could you please increase it?
Thanks!,
Rob
PS: Here some more data about the UPS:
The text was updated successfully, but these errors were encountered: