Fix ModbusBridge request/response logic #22075

Merged

Commits on Sep 2, 2024

  1. Fix ModbusBridge request/response logic

    - Fix cases where the subsequent Modbus packet
      can be send to the serial port (triggered either by
      'ModbusSend' command or request from TCP bridge)
      before an answer was received to the previous packet.
    
      This can happen in a setup where simultaneously:
      - two (or more) modbus TCP clients are sending requests
        through the modbus-proxy [1] to Tasmota,
      - ModbusSend commands are executed (e.g. using Berry).
    
      Log excerpt (from build with TASMOTAMODBUSDEBUG enabled):
      14:51:18.940 MBS: Serial Send: 04 03 01 00 00 09 84 65
      14:51:19.054 MBS: Serial Send: 04 03 10 0A 00 05 A1 5E
      14:51:19.136 MBS: Serial Received: 04 03 0A 00 00 00 D0 00 00 01 AB 00 00 89 62
    
      Fix adds 'waitingForAnswerFromSerial' flag which is set after
      we send data to the serial port and prevents sending another
      requests before we receive an answer or timeout happened.
    
      Fix stores temporarily a 'ModbusSend' command data and tries
      to execute it after Modbus response has been received or
      timeout has happened.
    
    - Add 'ModbusSerialTimeout' command which sets timeout in [ms]
      for how long we will be waiting for an answer from the client device.
      Default value is 1000 [ms] and it is not restored after reboot.
    
    - Sends error 11 (0xB) (as TCP response) when no answer was received
      from the serial port within the timeout set by 'ModbusSerialTimeout'
      command.
    
    - Add Modbus 'TransactionId' to the logging.
    
    [1] https://github.com/tiagocoutinho/modbus-proxy
    
    Signed-off-by: Damian Wrobel <[email protected]>