fix TotalHeatingCapacity, it missed cycling ratio
Browse files Browse the repository at this point in the history
  • Loading branch information
Yujie Xu committed Sep 19, 2024
1 parent 80732bf commit e4dcfb7
Showing 1 changed file with 2 additions and 2 deletions.
4 changes: 2 additions & 2 deletions src/EnergyPlus/HVACVariableRefrigerantFlow.cc
Original file line number Diff line number Diff line change
Expand Up @@ -12198,8 +12198,8 @@ void VRFCondenserEquipment::CalcVRFCondenser_FluidTCtrl(EnergyPlusData &state, c
}
}

this->TotalCoolingCapacity = TotalCondCoolingCapacity * CoolingPLR;
this->TotalHeatingCapacity = TotalCondHeatingCapacity * HeatingPLR;
this->TotalCoolingCapacity = TotalCondCoolingCapacity * CoolingPLR * CyclingRatio;
this->TotalHeatingCapacity = TotalCondHeatingCapacity * HeatingPLR * CyclingRatio;

if (this->MinPLR > 0.0) {
bool const plrTooLow = this->VRFCondPLR < this->MinPLR;
Expand Down