Skip to content

Computer composite power values for datacenters, rooms, rows and racks

License

Notifications You must be signed in to change notification settings

42ity/fty-metric-tpower

Repository files navigation

fty-metric-tpower

Agent fty-metric-tpower computes power metrics for racks and DCs.

How to build

To build fty-metric-tpower project run:

mkdir build && cd build
cmake -DCMAKE_BUILD_TYPE=Debug -DCMAKE_INSTALL_PREFIX=usr -DBUILD_TESTING=On ..
make
make check # to run self-test
sudo make install

How to run

To run fty-metric-tpower project:

  • from within the source tree, run:
./src/fty-metric-tpower

For the other options available, refer to the manual page of fty-metric-store

  • from an installed base, using systemd, run:
systemctl start fty-metric-tpower

Configuration file

Configuration file - fty-metric-tpower.cfg - is currently ignored.

Agent reads environment variable BIOS_LOG_LEVEL to set verbosity level.

Architecture

Overview

fty-metric-tpower has 1 actor:

  • fty-metric-tpower-server: main actor

It also has one built-in timer, which runs each minute, sends metrics for racks/DCS which request it and reloads the topology if reconfig was pending.

Protocols

Published metrics

Agent publishes power metrics for racks and DCs:

stream=METRICS
sender=agent-tpower
subject=realpower.default@rack-51
D: 18-01-19 13:30:18 FTY_PROTO_METRIC:
D: 18-01-19 13:30:18     aux=
D: 18-01-19 13:30:18     time=1516368615
D: 18-01-19 13:30:18     ttl=360
D: 18-01-19 13:30:18     type='realpower.default'
D: 18-01-19 13:30:18     name='rack-51'
D: 18-01-19 13:30:18     value='885.000000'
D: 18-01-19 13:30:18     unit='W'
stream=METRICS
sender=agent-tpower
subject=realpower.output.L1@datacenter-3
D: 18-01-19 13:30:18 FTY_PROTO_METRIC:
D: 18-01-19 13:30:18     aux=
D: 18-01-19 13:30:18     time=1516368617
D: 18-01-19 13:30:18     ttl=360
D: 18-01-19 13:30:18     type='realpower.output.L1'
D: 18-01-19 13:30:18     name='datacenter-3'
D: 18-01-19 13:30:18     value='1700.000000'
D: 18-01-19 13:30:18     unit='W'

Published alerts

Agent doesn't publish any alerts.

Mailbox requests

Agent doesn't receive any mailbox requests.

Stream subscriptions

METRICS stream

If the metric is not realpower metric, ignore it.

Otherwise, check whether the metric is relevant for any known rack/DC, recompute its power metrics and publish them if asked to do so.

ASSETS stream

On any ASSET message, postpone the reconfig if we are currently in the middle of one and set the timer to the next metric publish request.