Unsure if this the right place to post.. But, I'm seeing couple fields in OS:AirConditioner:VariableRefrigerantFlow object not properly being transferred to IDF.
Current Behavior
Below is the last 15 fields I have in the osm file:
Below is what I get for the same fields in the idf file (after running OS app):
Maximum Outdoor Temperature in Heat Recovery Mode switched from 20C to 30C. I couldn't find any description around this value being overridden from the documentation.
Initial Heat Recovery Cooling Capacity Fraction {W/W} switched from 0.5 to 1. I couldn't find any description around this value being overridden from the documentation.
Expected Behavior
I guess I just want to see the same values between osm and idf.
Issue overview
Unsure if this the right place to post.. But, I'm seeing couple fields in
OS:AirConditioner:VariableRefrigerantFlow
object not properly being transferred to IDF.Current Behavior
Below is the last 15 fields I have in the osm file:
Below is what I get for the same fields in the idf file (after running OS app):
Maximum Outdoor Temperature in Heat Recovery Mode
switched from 20C to 30C. I couldn't find any description around this value being overridden from the documentation.Initial Heat Recovery Cooling Capacity Fraction {W/W}
switched from 0.5 to 1. I couldn't find any description around this value being overridden from the documentation.Expected Behavior
I guess I just want to see the same values between osm and idf.
Steps to Reproduce
adding sample/example file here
Possible Solution
unsure