PMV follow up #8561
Merged
Merged
PMV follow up #8561
Changes from 13 commits
Commits
Show all changes
15 commits
Select commit
Hold shift + click to select a range
379db08
merge
xuanluo113 c1edf1d
Merge branch 'develop' of https://github.com/NREL/EnergyPlus into dev…
xuanluo113 e2f9130
Merge branch 'develop' of https://github.com/NREL/EnergyPlus into dev…
xuanluo113 121120f
Merge branch 'develop' of https://github.com/NREL/EnergyPlus into dev…
xuanluo113 c72d3fa
merge
xuanluo113 684e4c7
merge
xuanluo113 b8b445b
Merge branch 'develop' of https://github.com/NREL/EnergyPlus into dev…
xuanluo113 5d7f14c
Merge branch 'develop' of https://github.com/NREL/EnergyPlus into dev…
xuanluo113 034c0f8
address comments
xuanluo113 c9f020e
address comments part 2
xuanluo113 d6b4472
more documents
xuanluo113 24267ce
cmake
xuanluo113 c653eb7
fix a document
xuanluo113 0f4ff6e
Merge branch 'develop' of https://github.com/NREL/EnergyPlus into pmv…
xuanluo113 55c3309
address more comments
xuanluo113 File filter
Filter by extension
Conversations
Failed to load comments.
Loading
Jump to
Jump to file
Failed to load files.
Loading
Diff view
Diff view
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Loading
Sorry, something went wrong. Reload?
Sorry, we cannot display this file.
Sorry, this file is invalid so it cannot be displayed.
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
|
@@ -199,7 +199,35 @@ \subsubsection{Inputs}\label{inputs-025} | |
|
||
\paragraph{Field: Thermal Comfort Model Type (up to 7 allowed)}\label{field-thermal-comfort-model-type-up-to-7-allowed} | ||
|
||
The final one to five fields are optional and are intended to trigger various thermal comfort models within EnergyPlus. By entering the keywords Fanger, Pierce, KSU, AdaptiveASH55, AdaptiveCEN15251, CoolingEffectASH55, and AnkleDraftASH55, the user can request the Fanger, Pierce Two-Node, Kansas State UniversityTwo-Node, the adaptive comfort models of the ASHRAE Standard 55 and CEN Standard 15251, ASHRAE Standard 55 Elevated Air Cooling Effect model, and ASHRAE Standard 55 Ankle Draft Risk model results for this particular people statement. AdaptiveASH55 is only applicable when the running average outdoor air temperature for the past 7 days is between 10.0 and 33.5C. AdaptiveCEN15251 is only applicable when the running average outdoor air temperature for the past 30 days is between 10.0 and 30.0C. Note that since up to five models may be specified, the user may opt to have EnergyPlus calculate the thermal comfort for people identified with this people statement using all five models if desired. Note that the KSU model is computationally intensive and may noticeably increase the execution time of the simulation. For descriptions of the thermal comfort calculations, see the Engineering Reference document. | ||
The final one to five fields are optional and are intended to trigger various thermal comfort models within EnergyPlus. By entering the keywords Fanger, Pierce, KSU, AdaptiveASH55, AdaptiveCEN15251, CoolingEffectASH55, and AnkleDraftASH55, the user can request the Fanger, Pierce Two-Node, Kansas State UniversityTwo-Node, the adaptive comfort models of the ASHRAE Standard 55 and CEN Standard 15251, ASHRAE Standard 55 Elevated Air Cooling Effect model, and ASHRAE Standard 55 Ankle Draft Risk model results for this particular people statement. Detailed descriptions and requirements of the seven models as listed below. | ||
|
||
\begin{description} | ||
\item[Fanger] | ||
Fanger’s Comfort model is applied to calculate related thermal comfort metrics. Fanger Model PMV, PPD, and Clothing Surface Temperature are calculated and reported as each time step. Apart from existing required fields in People object, extra fields required for this model include Surface Name/Angle Factor List Name, Work Efficiency Schedule Name, Clothing Insulation Schedule Name, and Air Velocity Schedule Name. | ||
|
||
\item[Pierce] | ||
The Pierce Two-Node model is applied to calculate related thermal comfort metrics. Pierce Model Effective Temperature PMV, Standard Effective Temperature PMV, Discomfort Index, Thermal Sensation Index, and Standard Effective Temperature are calculated and reported as each time step.Apart from existing required fields in People object, extra fields required for this model include Surface Name/Angle Factor List Name, Work Efficiency Schedule Name, Clothing Insulation Schedule Name, and Air Velocity Schedule Name. | ||
|
||
\item[KSU] | ||
The KSU Two-Node Model is applied to calculate related thermal comfort metrics. KSU Model Thermal Sensation Vote is calculated and reported as each time step. Note that the KSU model is computationally intensive and may noticeably increase the execution time of the simulation. Apart from existing required fields in People object, extra fields required for this model include Surface Name/Angle Factor List Name, Work Efficiency Schedule Name, Clothing Insulation Schedule Name, and Air Velocity Schedule Name. | ||
|
||
\item[AdaptiveASH55] | ||
Adaptive Comfort Model Based on ASHRAE Standard 55-2010 is applied to calculate related thermal comfort metrics. ASHRAE 55 Adaptive Model 90\% Acceptability Status, 80\% Acceptability Status, Running Average Outdoor Air Temperature, and the Adaptive Model Temperature are calculated and reported as each time step. AdaptiveASH55 is only applicable when the running average outdoor air temperature for the past 7 days is between 10.0 and 33.5C. | ||
|
||
\item[AdaptiveCEN15251] | ||
Adaptive Comfort Model Based on European Standard EN15251-2007 is applied to calculate related thermal comfort metrics. CEN 15251 Adaptive Model Category I/II/II Status, Running Average Outdoor Air Temperature, and the Adaptive Model Temperature are calculated and reported as each time step. AdaptiveCEN15251 is only applicable when the running average outdoor air temperature for the past 30 days is between 10.0 and 30.0C. | ||
|
||
\item[CoolingEffectASH55] | ||
ASHRAE 55-2017 Elevated Air Speed Cooling Effect Model is applied to calculate related thermal comfort metrics. Elevated Air Speed Cooling Effect, Cooling Effect Adjusted PMV, and Cooling Effect Adjusted PPD are calculated and reported as each time step. Apart from existing required fields in People object, extra fields required for this model include Surface Name/Angle Factor List Name, Work Efficiency Schedule Name, Clothing Insulation Schedule Name, and Air Velocity Schedule Name. | ||
|
||
\item[AnkleDraftASH55] | ||
ASHRAE 55-2017 Ankle Draft Risk Model is applied to calculate related thermal comfort metrics. Zone Thermal Comfort ASHRAE 55 Ankle Draft PPD is calculated and reported as each time step. Apart from existing required fields in People object, extra fields required for this model include Surface Name/Angle Factor List Name, Work Efficiency Schedule Name, Clothing Insulation Schedule Name, Air Velocity Schedule Name, and Ankle Level Air Velocity Schedule Name. Ankle draft PPD calculations are only applicable for relative air velocity is below 0.2 m/s, and the subject’s metabolic rate and clothing level should be kept below 1.3 met and 0.7 clo. PPD at ankle draft will be set to -1.0 if if these conditions are not met. | ||
|
||
\end{description} | ||
|
||
For descriptions of the thermal comfort calculations, see the Engineering Reference document. | ||
|
||
Note that since up to seven models may be specified, the user may opt to have EnergyPlus calculate the thermal comfort for people identified with this people statement using all seven models if desired. | ||
|
||
|
||
\paragraph{Field: Ankle Level Air Velocity Schedule Name}\label{field-ankle-level-air-velocity-schedule-name} | ||
|
@@ -560,6 +588,22 @@ \subsubsection{Outputs}\label{outputs-017} | |
|
||
This field reports the ideal indoor operative temperature, or comfort temperature, as determined by the CEN-15251 adaptive comfort model. Category I, II, and II limits for indoor operative temperature are defined as no greater than 2, 3, and 4 degrees C from this value respectively. A value of -1 means not applicable (when running average outdoor temp is outside the range of 10.0 to 30.0C). | ||
|
||
\paragraph{Zone Thermal Comfort ASHRAE 55 Elevated Air Speed Cooling Effect}\label{zone-thermal-comfort-ashrae55-elevated-air-speed-cooling-effect} | ||
|
||
This field is the calculated Cooling Effect of the elevated air speed in degree celsius. It is the value that, when subtracted equally from both the average air temperature and the mean radiant temperature, yields the same SET under still air as in the first SET calculation under elevated air speed. | ||
|
||
\paragraph{Zone Thermal Comfort ASHRAE 55 Elevated Air Speed Cooling Effect Adjusted PMV}\label{zone-thermal-comfort-ashrae55-elevated-air-speed-cooling-effect-adjusted-pmv} | ||
|
||
This field is the \"predicted mean vote\" (PMV) calculated using the Fanger PMV model, adjusted by the ASHRAE 55 Elevated Air Speed Cooling Effect. The Cooling Effect adjusted PMV for an environment with elevated average air speed is calculated using the adjusted average air temperature, the adjusted radiant temperature, and still air (0.1 m/s). | ||
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. predicted is rendering as p̈redicted . Use the smart-quote characters (see existing entries further up): ``predicted mean vote'' (2 characters before and after). Same problem in the next two descriptions. |
||
|
||
\paragraph{Zone Thermal Comfort ASHRAE 55 Elevated Air Speed Cooling Effect Adjusted PPD}\label{zone-thermal-comfort-ashrae55-elevated-air-speed-cooling-effect-adjusted-ppd} | ||
|
||
This field is the \"ppredicted percentage of dissatisfied\" (PPD) calculated using the Fanger PMV-PPD model, adjusted by the ASHRAE 55 Elevated Air Speed Cooling Effect. The Cooling Effect adjusted PPD for an environment with elevated average air speed is calculated using the adjusted average air temperature, the adjusted radiant temperature, and still air (0.1 m/s). | ||
|
||
\paragraph{Zone Thermal Comfort ASHRAE 55 Ankle Draft PPD}\label{zone-thermal-comfort-ashrae55-ankle-draft-ppd} | ||
|
||
This field is the \"ppredicted percentage of dissatisfied\" (PPD) on draft at ankle level. It is used as the metric to evaluate the ankle draft risk as a function of PMV and air speed at the ankle level (0.1 m). | ||
|
||
\subsubsection{Outputs}\label{outputs-1-014} | ||
|
||
The following output variables are all based on whether the humidity ratio and the operative temperature is within the region shown in ASHRAE Standard 55-2004 in Figure 5.2.1.1. For these outputs the operative temperature is simplified to be the average of the air temperature and the mean radiant temperature. For summer, the 0.5 Clo level is used and, for winter, the 1.0 Clo level is used. The graphs below are based on the following tables which extend the ASHRAE values to zero humidity ratio. | ||
|
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Oops, something went wrong.
Add this suggestion to a batch that can be applied as a single commit.
This suggestion is invalid because no changes were made to the code.
Suggestions cannot be applied while the pull request is closed.
Suggestions cannot be applied while viewing a subset of changes.
Only one suggestion per line can be applied in a batch.
Add this suggestion to a batch that can be applied as a single commit.
Applying suggestions on deleted lines is not supported.
You must change the existing code in this line in order to create a valid suggestion.
Outdated suggestions cannot be applied.
This suggestion has been applied or marked resolved.
Suggestions cannot be applied from pending reviews.
Suggestions cannot be applied on multi-line comments.
Suggestions cannot be applied while the pull request is queued to merge.
Suggestion cannot be applied right now. Please check back later.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Very minor question. Here Va is upper case for air speed, but the other air speeds below are all lower-case v. Is that intentional?